What Causes Intermittent Underground Cable Faults and How Can You Find Them?

Learn the causes and symptoms of intermittent underground cable faults, how to diagnose them, and which cable testing methods can help locate them.

An intermittent underground cable fault is an electrical problem that appears and disappears under certain operating conditions.

The cable may work normally for a period and then experience a power interruption, insulation failure, or protection trip. When technicians test the cable after the fault disappears, the measurement may return to a normal or unstable result.

This makes intermittent faults more difficult to diagnose than permanent open-circuit or short-circuit faults.

Click the image to know more about Wrindu RDCD-C Vehicle-Mounted Cable Fault Testing System.

What Is an Intermittent Cable Fault?

An intermittent cable fault is a temporary electrical fault that does not remain continuously present.

The fault condition may change with temperature, mechanical movement, moisture, electrical stress, or operating voltage.

For example, a damaged conductor may make electrical contact when the cable moves slightly. The connection may then separate again when the cable returns to its original position.

The fault may therefore be difficult to reproduce during a single measurement.

What Causes Intermittent Underground Cable Faults?

Several conditions can cause an underground cable fault to appear and disappear.

Cause How it affects the cable
Loose cable connection Electrical contact changes with movement or vibration
Damaged insulation Electrical breakdown occurs under certain voltage conditions
Thermal expansion Temperature changes affect damaged joints or connections
Water ingress Moisture changes the insulation condition
Mechanical stress Cable movement changes contact at a damaged point
Aging cable accessories Deteriorated joints or terminations may develop unstable electrical contact

The actual cause depends on the cable construction, installation environment, and operating history.

What Are the Common Signs of an Intermittent Cable Fault?

Intermittent faults often produce unstable operating conditions rather than one permanent failure.

Common signs include:

  • Repeated but irregular circuit breaker trips.
  • Power interruptions without a clear pattern.
  • Insulation resistance readings that change between tests.
  • Fault indications that disappear after the cable cools down.
  • Electrical problems that occur only under load or certain voltage conditions.

These symptoms do not confirm the fault location. Technicians need additional testing to identify the damaged section.

Why Are Intermittent Cable Faults Difficult to Locate?

The main difficulty is that the fault may not be active during testing.

A TDR instrument detects impedance changes through reflected electrical pulses. If the intermittent fault is not electrically present when the pulse is sent, the waveform may not show a clear fault reflection.

A cable may therefore produce different waveforms during different measurements.

Another difficulty is that the fault may only appear under operating voltage or temperature conditions that are not present during routine testing.

How Do You Diagnose an Intermittent Underground Cable Fault?

Technicians should first collect information about when and how the fault occurs.

A structured diagnosis can reduce unnecessary testing.

Step 1: Review the fault history

Record the time, frequency, operating load, weather conditions, and protection events associated with each interruption.

Step 2: Inspect cable joints and terminations

Check accessible joints, terminations, and connections for visible damage, moisture, contamination, or loose components.

Step 3: Perform insulation resistance testing

Measure the insulation resistance between conductors and between conductors and earth, following the appropriate test procedure.

Step 4: Compare repeated measurements

Record the test conditions and compare the results. Large changes may indicate an unstable insulation or connection condition.

Step 5: Select a suitable fault location method

Use TDR or another appropriate method based on whether the fault can produce a detectable reflection or discharge.

A single normal test result does not rule out an intermittent fault.

Can TDR Detect Intermittent Cable Faults?

TDR can locate an intermittent fault when the fault produces a detectable impedance change during measurement.

However, if the fault is inactive, the reflected signal may not reveal its position.

Repeated measurements can help identify changes in the waveform. Technicians can compare the results to determine whether the fault condition is stable or intermittent.

If low-voltage TDR does not provide a clear result, another suitable testing method may be needed.

When Is High-Voltage Testing Needed for Intermittent Cable Faults?

Some intermittent faults are related to insulation defects that become conductive only under sufficient electrical stress.

In these cases, a suitable high-voltage test may help reproduce the fault condition.

A surge generator can apply a controlled impulse to a suitable cable fault. If a discharge occurs, the resulting signal may support fault pre-location or ground pinpointing.

However, high-voltage testing is not appropriate for every intermittent fault. A loose connection or mechanically unstable joint may require inspection and other diagnostic methods instead.

The test voltage and energy must follow the cable and equipment requirements.

What Is the Difference Between Intermittent and Permanent Cable Faults?

The main difference is whether the electrical fault remains continuously present.

Comparison Intermittent Fault Permanent Fault
Fault condition Appears and disappears Remains present
Electrical behavior Changes over time Relatively stable
Test results May vary between measurements Usually show a consistent abnormal condition
Typical causes Loose contact, unstable insulation, thermal or mechanical changes Broken conductor, permanent short circuit, severe insulation damage
Diagnosis May require repeated testing Often easier to confirm through initial electrical tests
Fault location Can be difficult if inactive Usually easier when the fault produces a clear signal

An intermittent fault can eventually become a permanent fault if the underlying damage continues to develop.

How Can You Prevent Intermittent Underground Cable Faults?

Regular inspection and proper installation can reduce the risk of intermittent cable problems.

Maintenance teams should focus on the following areas:

Maintenance measure Purpose
Inspect cable joints Identify loose or damaged connections
Check cable terminations Find signs of moisture or insulation deterioration
Monitor insulation condition Detect changes in electrical insulation performance
Review protection records Identify repeated or irregular fault events
Check cable installation Reduce mechanical stress and damage
Keep maintenance records Compare historical test results and identify changes

Inspection intervals should follow the cable manufacturer’s recommendations, operating conditions, and applicable maintenance requirements.

Which Equipment Is Used to Diagnose Intermittent Cable Faults?

Different instruments provide different types of information.

Equipment Main function
Insulation resistance tester Checks insulation resistance
TDR cable fault tester Detects impedance changes and estimates reflection distance
High-voltage test equipment Applies controlled electrical stress for suitable fault diagnosis
Acoustic-magnetic locator Helps pinpoint a detectable discharge above ground
Cable path detector Identifies the underground cable route

The equipment should be selected according to the suspected fault mechanism. No single instrument can identify every intermittent cable problem.

Frequently Asked Questions About Intermittent Cable Faults

Can an intermittent cable fault disappear during testing?

Yes. If the fault is inactive during measurement, the test result may appear normal. Repeated testing and a review of operating records can help identify the problem.

Can TDR locate an intermittent cable fault?

Yes, when the fault creates a detectable impedance change during measurement. If the fault is inactive, TDR may not show a clear reflection.

Can temperature cause intermittent cable faults?

Yes. Temperature changes can affect damaged joints, connections, and insulation. Thermal expansion may change the electrical contact at an existing defect.

Can a loose cable joint cause intermittent faults?

Yes. A loose or damaged connection may make and break electrical contact as the cable or connection changes with vibration, movement, or temperature.

Does an intermittent cable fault always become permanent?

No. However, an unresolved fault may cause further deterioration and eventually develop into a permanent electrical failure.

What should technicians do when insulation resistance readings keep changing?

They should verify the test connections, test conditions, and cable isolation. If the readings remain unstable, further diagnosis is required to identify the cause.

About Wrindu Cable Fault Testing Equipment

Wrindu is a Chinese OEM manufacturer of electrical testing equipment and power testing solutions. Its cable fault testing equipment supports cable testing, fault pre-location, and field diagnosis.

The RDCD-C Vehicle-Mounted Cable Fault Testing System combines different cable testing instruments in one vehicle-mounted setup. It is designed for power utilities and cable maintenance teams.

The system is supplied without a vehicle. Customers can select a suitable vehicle based on their working environment and installation requirements.

For more information, visit the RDCD-C Vehicle-Mounted Cable Fault Testing System.

wrindu
wrindu